Retningslinjer for håndtering og udskiftning af kortslutningsfejl i strømkondensatorens interne kondensatorelementer

Jul 11, 2025|

Power capacitors, as indispensable reactive power compensation devices in power systems, play a significant role in improving power factor, enhancing voltage quality, and reducing line losses. However, during long-term operation, the internal capacitor elements of power capacitors may experience short-circuit faults due to various reasons, seriously affecting the performance and safe operation of the equipment. So, how should we håndtere det?

 

I . fejlfunktionsgenkendelse og nødhåndtering

1. Typiske manifestationer af kortslutningsfejl:

Huset af strømkondensatoren er unormalt hævet eller lækker olie .

En unormal decharge -lyd udsendes under drift .

Temperaturovervågningen indikerer lokaliseret overophedning (ΔT> 15K);

Beskyttelsesenheden fungerer ofte (overstrøm/ubalancebeskyttelse) .

2. Emergency Response Procedures:

① Afskær straks strømforsyningen i kredsløbet, hvor strømkondensatoren er placeret .
② Aktivér backup -kompensationskredsløbet (hvis nogen)
③ Opret et sikkerhedsisoleringsområde (med en radius på ikke mindre end 5 meter)
④ Brug en infrarød termisk billedbillede til at bekræfte placeringen af fejlen

II . Fejlkomponentdetektionsteknologi

1. Professionelle testmetoder:

Måling af kapacitansværdi (afvigelse af defekt fase> ± 10%);

Dielektrisk tabstest (Tanδ -værdi overstiger værdien for nyt produkt med 200%);

DC modstå spændingstest (lækage strøm> 50μA ved 2un DC spænding) .

2. Diagnostiske kriterier:

Det betragtes som en komponent kortslutning, hvis den opfylder begge følgende betingelser:

① Isoleringsmodstand <100 MΩ (målt med et 2500V multimeter)
② Kapacitansværdien er steget med mere end 20%.