Retningslinjer for håndtering og udskiftning af kortslutningsfejl i strømkondensatorens interne kondensatorelementer
Jul 11, 2025| Power capacitors, as indispensable reactive power compensation devices in power systems, play a significant role in improving power factor, enhancing voltage quality, and reducing line losses. However, during long-term operation, the internal capacitor elements of power capacitors may experience short-circuit faults due to various reasons, seriously affecting the performance and safe operation of the equipment. So, how should we håndtere det?
I . fejlfunktionsgenkendelse og nødhåndtering
1. Typiske manifestationer af kortslutningsfejl:
Huset af strømkondensatoren er unormalt hævet eller lækker olie .
En unormal decharge -lyd udsendes under drift .
Temperaturovervågningen indikerer lokaliseret overophedning (ΔT> 15K);
Beskyttelsesenheden fungerer ofte (overstrøm/ubalancebeskyttelse) .
2. Emergency Response Procedures:
① Afskær straks strømforsyningen i kredsløbet, hvor strømkondensatoren er placeret .
② Aktivér backup -kompensationskredsløbet (hvis nogen)
③ Opret et sikkerhedsisoleringsområde (med en radius på ikke mindre end 5 meter)
④ Brug en infrarød termisk billedbillede til at bekræfte placeringen af fejlen
II . Fejlkomponentdetektionsteknologi
1. Professionelle testmetoder:
Måling af kapacitansværdi (afvigelse af defekt fase> ± 10%);
Dielektrisk tabstest (Tanδ -værdi overstiger værdien for nyt produkt med 200%);
DC modstå spændingstest (lækage strøm> 50μA ved 2un DC spænding) .
2. Diagnostiske kriterier:
Det betragtes som en komponent kortslutning, hvis den opfylder begge følgende betingelser:
① Isoleringsmodstand <100 MΩ (målt med et 2500V multimeter)
② Kapacitansværdien er steget med mere end 20%.